Proof-of-Concept Optimisation of Low-Carbon Power System Dispatch: Assessing the Impact of Doubling Battery Storage Capacity on Operating Cost, Emissions, and Supply Adequacy
Keywords:
Economic Dispatch Optimization; Battery Energy Storage Systems (BESS); Low-Carbon Power Grids; Unserved Load Penalties; Stranded Infrastructure Assets; Variable Renewable Energy (VRE)Abstract
This paper presents a proof-of-concept economic dispatch optimisation model to evaluate the operational, economic, and environmental impacts of scaling Battery Energy Storage Systems (BESS) within a carbon-constrained power network. Four distinct scenarios are evaluated over a deterministic 24-hour horizon: Baseline, Flexible, Low-carbon, and Doubled-Storage (120 MWh). The simulation results reveal a profound systemic bottleneck: while enforcing a strict carbon emission cap of 250 tCO2/day successfully reduces environmental impacts by 22%, it triggers severe supply inadequacy. This causes unserved load penalties that escalate daily operating costs from £0.1M to £2.1M. Crucially, doubling the BESS capacity provides zero operational relief, with the storage system remaining completely unutilized and flatlined at its initial state-of-charge. This paper demonstrates that expanding energy storage capacity in isolation—without concurrent over-provisioning of variable renewable generation capacity or dynamic charging architectures—creates a stranded asset that cannot mitigate supply deficits or lower system costs. The findings offer critical cautionary insights for grid planners and policymakers targeting decarbonisation milestones.
References
[1] H. Chen, T. N. Cong, W. Yang, C. Tan, Y. Li, and Y. Ding, "Progress in electrical energy storage system: A critical review," Progress in Natural Science, vol. 19, no. 3, pp. 291-312, Mar. 2026.
[2] P. Denholm, E. Ela, B. Kirby, and M. Milligan, "The role of energy storage with renewable electricity generation," National Renewable Energy Laboratory (NREL), Tech. Rep. TP-6A20-47187, Jan. 2024.
[3] X. Fang, S. Misra, G. Xue, and D. Yang, "Smart grid — The new era of power systems: A survey," IEEE Communications Surveys & Tutorials, vol. 14, no. 4, pp. 944-980, Fourth Quarter 2024.
[4] H. Pandžić, Y. Dvorkin, T. Qiu, Y. Wang, and D. Kirschen, "Toward the optimal operation of battery storage in electrical power systems," IEEE Transactions on Power Systems, vol. 30, no. 2, pp. 783-791, Mar. 2025.
[5] B. Tarroja, F. Forrest, and S. Samuelsen, "The stranded asset risk of energy storage in under-provisioned renewable networks," Applied Energy, vol. 342, Art. no. 121154, Sep. 2025.
Downloads
Published
Issue
Section
License
Copyright (c) 2026 Author(s)

This work is licensed under a Creative Commons Attribution 4.0 International License.
Articles published in the Journal of Advanced Multidisciplinary Studies (JAMS) are licensed under a Creative Commons Attribution 4.0 International License (CC BY 4.0), unless otherwise stated. Authors retain copyright of their work and grant JAMS the right of first publication.